ETL2-63 3P+N three-phase RCBO front view
ETL2-63 3P+N three-phase RCBO front view
ETL2-63 3P+N

RCBO for Three-Phase Circuit Protection

ETL2-63 3P+N RCBO combines residual current, overload and short-circuit protection in a compact 54mm device. Designed for 400/415V three-phase distribution systems, it is available with 6kA or 10kA breaking capacity, Type AC or Type A residual current detection, and B, C or D tripping curves.

  • Breaking capacity: 6kA, 10kA
  • Voltage: 240/415V AC systems (50/60Hz)
  • Current range: 6A to 63A
  • Rated residual current: 10, 30, 100, 300mA
  • Tripping curves: Type B/C/D available
  • Electronic type
  • Bidirectional wiring capability
  • AC and A types
  • Transparent trip status observation port
  • RCBO according to IEC/EN 61009-1
Informe-se AGORA PDF

RCBO for Three-Phase Circuit Protection

Informe-se AGORA PDF

Visão geral do produto

Compact 3-Phase RCBO for Distribution Systems

ETL2-63 3P+N series combines thermal-magnetic overload and short-circuit protection with electronic residual current protection in a compact 54 mm, three-module DIN-rail device.

Designed for 400/415 V AC three-phase circuits, it is suitable for residential, commercial, and industrial distribution boards. The series complies with IEC/EN 61009-1. The ETL2-63 offers a rated short-circuit breaking capacity of 6 kA, while the ETL2-63H provides 10 kA. The neutral line is unswitched.

 

Key Features

Combined Circuit Protection

Provides earth fault, overload and short-circuit protection in one device.

Three-Phase Configuration

3P+N design for 400/415V AC systems, with an unswitched neutral.

Compact Dimensions

54mm-wide, three-module design for distribution boards.

6kA or 10kA Breaking Capacity

Select ETL2-63 for 6kA or ETL2-63H for 10kA.

Type AC and Type A Options

Select the residual current type according to the installation and connected loads.

B, C and D Tripping Curves

Available for different load characteristics.

Bidirectional Wiring

Line and load connections are interchangeable as specified in the product documentation.

Easy Status Checking

Equipped with a test button and contact position indicator.

DIN-Rail Installation

Suitable for mounting on a 35mm DIN rail.

Accessory Support

Compatible with selected auxiliary contacts, alarm contacts and release devices.

 

Frequently Asked Questions

What is a 3P+N RCBO?

A 3P+N RCBO is a residual current circuit breaker with overcurrent protection intended for a three-phase system with a neutral conductor. It combines residual current protection with overload and short-circuit protection. On the ETL2-63(H) 3P+N, the neutral line is unswitched.

What is the difference between ETL2-63 and ETL2-63H?

The ETL2-63 has a rated short-circuit breaking capacity of 6kA, while the ETL2-63H has a rated short-circuit breaking capacity of 10kA.

Is the ETL2-63(H) 3P+N RCBO available in Type A?

Yes. The product series offers Type A and Type AC residual current detection. Please confirm the availability of your required specification before ordering.

Which tripping curves are available for the 3P+N version?

The 3P+N version offers B, C and D tripping curves. The appropriate curve depends on the load characteristics and installation requirements.

Does this RCBO switch the neutral?

No. The neutral line of the ETL2-63(H) 3P+N RCBO is unswitched. If neutral switching or isolation is required, select a device suitable for that requirement.

Parâmetros técnicos

Technical Data

Technical Data

Standard

IEC/EN 61009-1

Protection

Ground fault, overcurrent and short circuit

Type of trip

Ground fault: Electronic

Overload and short circuit:Thermal-magnetic

Residual current type

AC type: AC residual current

A type: Residual AC and pulsating DC current

No. of poles

3P+N, neutral line is unswitched

Insulation voltage (Ui)

500V

Rated voltage (Ue)

400/415V~

Rated currents (In)

6, 10, 16, 20, 25, 32, 40, 50, 63A

Rated sensitivity currents (IΔn)

10, 30, 100, 300mA

Residual current off-time under IΔn

≤0.1s

Rated residual making and breaking capacity (IΔm)

500A (In ≤ 50A); 10In (In > 50A)

Rated frequency

50/60Hz

Rated short-circuit capacity (Icn)

ETL2-63: 6kA; ETL2-63H: 10kA

Energy limiting class

3

Rated impulse withstand voltage (Uimp) (1.2/50μs)

4kV

Dielectric test voltage

2kV (50/60Hz, 1 min.)

Fire resistance (glow-wire test)

960 ± 15°C (enclosure); 650 ± 10°C (handle)

Thermal tripping characteristics

1.13In: no tripping within an hour; 1.45In: tripping within an hour

Instantaneous tripping characteristics

B: 3In–5In; C: 5In–10In; D: 10In–20In

Electrical life

4,000 cycles

Mechanical life

8,000 cycles

Contact position indicator

Green OFF / Red ON

Protection degree

IP20

Ambient temperature

−25°C to +55°C

Storage temperature

−30°C to +70°C

Top terminals connection type

Cable / Pin-type busbar

Bottom terminals connection type

Cable / Pin-type / Fork-type busbar

Max. Top terminal size for cable

25mm²

Max. Bottom terminal size for cable

25mm²

Max.Top tightening torque

2.0N·m

Max. Bottom tightening torque

2.5N·m

Neutral load cable

Blue, 455mm length, 4mm²; other lengths available upon request

Installation

Mounting on 35mm DIN rail

Wiring method

Bi-Directional

Auxiliary Contact

Yes

Auxiliary & Alarm Contact

Yes

Shunt Release

Yes

Shunt Release & Auxiliary Contact

Yes

Voltage Loss Release

Yes

Over-voltage Release

Yes

Undervoltage Release

Yes

Over-undervoltage Release

Yes